ASTM B640-12
Historical Standard: ASTM B640-12 Standard Specification for Welded Copper Tube for Air Conditioning and Refrigeration Service
SUPERSEDED (see Active link, below)
ASTM B640
1. Scope
1.1 This specification establishes the requirements for welded copper tube for air conditioning and refrigeration service for use in connections, repairs, and alterations. The tube shall be made from one of the following coppers:
Copper UNS No. | Previously Used Designation | Type of Copper |
C10100 | OFE | Oxygen-free electronic |
C10200 | OF | Oxygen-free without-residual oxidants |
C12000 | DLP | Phosphorus-deoxidized, low-residual phosphorus |
C12200 | DHP | Phosphorus-deoxidized, high-residual phosphorus |
Note 1Fittings used for soldered or brazed connections in air conditioning and refrigeration systems are described in ASME Standard B 16.22.
Note 2The assembly of copper tubular systems by soldering is described in Practice B828 .
Note 3Solders for joining copper tubular systems by descirbed in Specification B32 . The requirements for acceptable fluxes for these systems are described in Specification B813 .
1.2 Copper UNS No. C12200 shall be furnished, unless otherwise specified. The copper tube shall be supplied in annealed coils or drawn temper straight lengths.
1.3 Units Values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units which are provided for information only and are not considered standard.
1.4 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.
2. Referenced Documents (purchase separately) The documents listed below are referenced within the subject standard but are not provided as part of the standard.
ASTM Standards
B32 Specification for Solder Metal
B153 Test Method for Expansion (Pin Test) of Copper and Copper-Alloy Pipe and Tubing
B170 Specification for Oxygen-Free Electrolytic Copper--Refinery Shapes
B577 Test Methods for Detection of Cuprous Oxide (Hydrogen Embrittlement Susceptibility) in Copper
B601 Classification for Temper Designations for Copper and Copper Alloys--Wrought and Cast
B813 Specification for Liquid and Paste Fluxes for Soldering of Copper and Copper Alloy Tube
B828 Practice for Making Capillary Joints by Soldering of Copper and Copper Alloy Tube and Fittings
B846 Terminology for Copper and Copper Alloys
B900 Practice for Packaging of Copper and Copper Alloy Mill Products for U.S. Government Agencies
B968/B968M Test Method for Flattening of Copper and Copper-Alloy Pipe and Tube
E3 Guide for Preparation of Metallographic Specimens
E8/E8M Test Methods for Tension Testing of Metallic Materials
E29 Practice for Using Significant Digits in Test Data to Determine Conformance with Specifications
E53 Test Method for Determination of Copper in Unalloyed Copper by Gravimetry
E62 Test Methods for Chemical Analysis of Copper and Copper Alloys (Photometric Methods)
E243 Practice for Electromagnetic (Eddy-Current) Examination of Copper and Copper-Alloy Tubes
E255 Practice for Sampling Copper and Copper Alloys for the Determination of Chemical Composition
E527 Practice for Numbering Metals and Alloys in the Unified Numbering System (UNS)
ASME Standards
B 16.22 Wrought Copper and Copper Alloy Solder Joint Pressure FittingsKeywords
air conditioning tube; refrigeration tube; welded copper tube; UNS No. C10100; UNS No. C10200; UNS No. C12000; UNS No. C12200; ICS Number Code 2200; 77.150.30 (Copper products)
DOI: 10.1520/B0640-12