ASTM D93-02a
Historical Standard: ASTM D93-02a Standard Test Methods for Flash-Point by Pensky-Martens Closed Cup Tester
SUPERSEDED (see Active link, below)
ASTM D93
1. Scope
1.1 This test method covers the determination of the flash point of petroleum products in the temperature range from 40 to 360 o C by a manual Pensky-Martens closed-cup apparatus or an automated Pensky-Martens closed-cup apparatus.
Note 1Flash point determination as above 250 o C can be performed, however, the precisions have not been determined above this temperature. For residual fuels, precisions have not been determined for flash points above 100 o C.
1.2 Procedure A is applicable to distillate fuels (diesel, kerosene, heating oil, turbine fuels), new lubricating oils, and other homogeneous petroleum liquids not included in the scope of Procedure B.
1.3 Procedure B is applicable to residual fuel oils, cutback residua, used lubricating oils, mixtures of petroleum liquids with solids, petroleum liquids that tend to form a surface film under test conditions, or are petroleum liquids of such kinematic viscosity that they are not uniformly heated under the stirring and heating conditions of Procedure A.
Note 2--Liquids having kinematic viscosities less than 5.5 mm 2/s (cSt) at 40 o C (104 o F), do not contain suspended solids, or do not have a tendency to form a surface film while under test conditions, can be tested in accordance with Test Method D56.
1.4 This test method is applicable for the detection of contamination of relatively nonvolatile or nonflammable materials with volatile or flammable materials.
1.5 The values stated in SI units shall be regarded as the standard. The values given in parentheses are provided for information only.
1.6 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. For specific hazards statements, see 6.4, 7.1, 9.3, 9.4, 11.1.2, 11.1.4, and 12.1.2
2. Referenced Documents (purchase separately) The documents listed below are referenced within the subject standard but are not provided as part of the standard.
ASTM Standards
D56 Test Method for Flash Point by Tag Closed Cup Tester
D3941 Test Method for Flash Point by the Equilibrium Method With a Closed-Cup Apparatus
D4057 Practice for Manual Sampling of Petroleum and Petroleum Products
D4177 Practice for Automatic Sampling of Petroleum and Petroleum Products
E1 Specification for ASTM Liquid-in-Glass Thermometers
E300 Practice for Sampling Industrial Chemicals
E502 Test Method for Selection and Use of ASTM Standards for the Determination of Flash Point of Chemicals by Closed Cup Methods
ISO Standards
Guide 35 Certification of Reference Material--General and Statistical PrinciplesKeywords
automated flash point; automated Pensky-Martens closed cup; flammability; flash point; Pensky-Martens closed cup;
ICS Code
ICS Number Code 13.220.40 (Ignitability and burning behaviour of materials and products); 75.080 (Petroleum products in general); 75.160.20 (Liquid fuels)
DOI: 10.1520/D0093-02A