Already a subscriber? 

MADCAD.com Free Trial
Sign up for a 3 day free trial to explore the MADCAD.com interface, PLUS access the
2009 International Building Code to see how it all works.
If you like to setup a quick demo, let us know at support@madcad.com
or +1 800.798.9296 and we will be happy to schedule a webinar for you.
Security check
Please login to your personal account to use this feature.
Please login to your authorized staff account to use this feature.
Are you sure you want to empty the cart?

City of Santa Cruz Ordinance 2022-014: Amendments to 2022 California Codes, 2022
- [A] 109.6 – Overcrowding. Overcrowding or admittance of any person beyond the approved capacity of a building or a portion thereof shall not be allowed. The fire code official, upon finding any overcrowding conditions or obstructions in aisles, passag...
- “19.05.070 SECTION [A] 112.4 IS ADDED– VIOLATION PENALTIES.
- “19.05.080 SECTION [A] 112.4.1 AMENDED AND 112.4.2 ADDED—ABATEMENT OF VIOLATION; FAILURE TO COMPLY.
- STATE RESPONSIBILITY AREA (SRA) shall mean lands that are classified by the Board of Forestry pursuant to Public Resources Code Section 4125 to 4127; and the California Code of Regulations, Title14, Division 1.5, Chapter 7, Article 1, Sections 1220-12...
- “19.05.100 SECTION 304.1.2 IS AMENDED – VEGETATION.
- “19.05.200 SECTION 507.1 IS AMENDED – REQUIRED WATER SUPPLY.
- “19.05.220 CFC SECTIONS 903.1 THROUGH 903.2.10.2 ARE DELETED AND REPLACED – AUTOMATIC SPRINKLER SYSTEMS.
- Section 903.3.1.1.2 of Chapter 9 of the Fire Code of the city of Santa Cruz is deleted.”
- “19.05.240 SECTION 1103.5.5 IS ADDED – PYROXYLIN PLASTICS.
- “19.05.260 SECTION 3905.1.1 IS AMENDED – SAFETY SYSTEMS
- Section 3905.1.1 of Chapter 39 of the Fire Code of the city of Santa Cruz is amended to read as follows:
- 3905.1.1 – Operation. Activation of the gas detection system shall result in all of the following:
- 1. Initiation of distinct audible and visual alarm signals in extraction room.
- 2. Deactivation of all heating systems located in the extraction room.
- 3. Activation of the mechanical ventilation system, where the system is interlocked with gas detection.
- 4. De-energize all light switches and electrical outlets.
- 5. For detection levels at or exceeding 25% of the LEL/LFL shall result in the activation of the building’s fire alarm system.”
- “19.05.270 SECTION 4901.3 IS ADDED – REQUIREMENTS FOR WILDLAND-URBAN INTERFACE FIRE AREAS.
- Section 4901.3 of Chapter 49 of the Fire Code of the city of Santa Cruz is added to read as follows:
- 4901.3 General. Areas identified within the Wildland-Urban Interface, as determined by the Fire Code Official, shall be held to all requirements as defined in Sections 4902.1 through 4910.4.
- 1. As determined by the Fire Code Official, construction requirements as identified in California Building Code, Chapter 7A, California Residential Code, Section R337 and California Referenced Standards Code, Chapter 12-7A shall apply to:
- a) All new construction
- b) All new materials used for additions and remodels.”
- “19.05.310 CHAPTER 90 IS ADDED – SUPPRESSION AND CONTROL OF WILDFIRE RISK AREAS. [Go to Page]